Description
| ELECTRICAL | |
| Voltage | 24 V DC |
| Operational voltage | <= 690 V <= 400 Hz |
| Permissible current | 10 A for relay output |
| Pole | 2NO + 2NC |
| Aplication | Control relay |
| Insulation voltage | 600 V conforming to CSA C22.2 No 14 690 V conforming to BS 5424 690 V conforming to IEC 60947 750 V conforming to VDE 0110 group C |
| Control circuit voltage limit | 0.8…1.15 Uc at 50 °C operational 0.1…0.75 Uc at 50 °C drop-out |
| Minimum switching Voltage & Current | 17 V / 5 mA |
| mechanical | |
| Protection | |
| Dimension | H58 X W45 X D57 mm |
| Weight | 225 g |
| Compatibility | |
| Connection | Screw clamp terminals 1 cable(s) 1.5…4 mm² – cable stiffness: solid Screw clamp terminals 2 cable(s) 1.5…4 mm² – cable stiffness: solid Screw clamp terminals 2 cable(s) 0.75…4 mm² – cable stiffness: flexible – without cable end Screw clamp terminals 1 cable(s) 0.75…4 mm² – cable stiffness: flexible – with cable end Screw clamp terminals 1 cable(s) 0.34…1.5 mm² – cable stiffness: flexible – with cable end Screw clamp terminals 2 cable(s) 0.34…1.5 mm² – cable stiffness: flexible – without cable endx |
| Safety | Vibrations contactor closed 4 Gn, 5…300 Hz IEC 60068-2-6 Vibrations contactor open 2 Gn, 5…300 Hz IEC 60068-2-6 Shocks contactor open 10 Gn for 11 ms IEC 60068-2-27 Shocks contactor closed 15 Gn for 11 ms IEC 60068-2-27 |
| Durability | 20 Mcycles |
| material | |
| Type | |
| Safety reliability | V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102 |
| Mounting support | Plate
Rail |
| envorinmental | |
| Protection | TH conforming to IEC 60068-2-30 |
| Standard | ATEX D 94/9/CE EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 CSA C22.2 No 14 |
| IP protection | IP20 front face conforming to IEC 60529
IP40 (enclosure) conforming to EN/IEC 60529 |
| Certification | ATEX INERIS BV CCC CSA DNV GL GOST LROS (Lloyds register of shipping) RINA UL |
| Temperature range | -60 °C to +70 ° |



Reviews
There are no reviews yet.