0.72 A at 500 V AC-15 for signalling circuit
0.06 A at 440 V DC-13 for signalling circuit
Temperature
-20…60 °C
Motor power
phases motors
Pole
3 Pole NO/NC
Auxilary contact
2
Insulation voltage
1000 V power circuit conforming to IEC 60947-4-1
600 V power circuit conforming to CSA
600 V power circuit conforming to UL
mechanical
Protection
Dimension
H173 X W75 X D121 mm
Weight
510 g
Connection
Power circuit : screw clamp terminals 1 cable(s) 4…35 mm² flexible without cable end
Power circuit : screw clamp terminals 1 cable(s) 4…35 mm² flexible with cable end
Power circuit : screw clamp terminals 1 cable(s) 4…35 mm² solid without cable end
Control circuit : screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end
Control circuit : screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end
Control circuit : screw clamp terminals 2 cable(s) 1…2.5 mm² solid without cable end
Tightening torque
Control circuit : 1.7 N.m on screw clamp terminals
Power circuit : 9 N.m on screw clamp terminals
Tripping threshold
1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Sensitivity
Tripping current 130 % of Ir on two phase, the last one at 0
material
Coil
Controle
Red push-button stop
Blue push-button for reset mode
Mounting support
Plate with specific accessories
Rail with specific accessories
Under contactor
envorinmental
Protection
TH conforming to IEC 60068-2-30
Standard
ATEX D 94/9/CE
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
CSA C22.2 No 14
IP protection
IP20 front face conforming to IEC 60529
Certification
ATEX INERIS BV CCC CSA DNV GL GOST
LROS (Lloyds register of shipping)
RINA UL