| ELECTRICAL |
| Voltage |
440 VAC 50/60 Hz |
| Operational current |
12 A |
| Power |
45 kW |
| Reliability |
7.5 kW at 500 V AC 50/60 Hz AC-3
7.5 kW at 660…690 V AC 50/60 Hz AC-3
5.5 kW at 380…400 V AC 50/60 Hz AC-3
5.5 kW at 415…440 V AC 50/60 Hz AC-3
3 kW at 220…230 V AC 50/60 Hz AC-3
3.7 kW at 400 V AC 50/60 Hz AC-4 |
| Motor power |
2 hp at 230/240 V AC 50/60 Hz 1 phase motors
3 hp at 200/208 V AC 50/60 Hz 3 phases motors
3 hp at 230/240 V AC 50/60 Hz 3 phases motors
7.5 hp at 460/480 V AC 50/60 Hz 3 phases motors
10 hp at 575/600 V AC 50/60 Hz 3 phases motors
0.5 hp at 115 V AC 50/60 Hz 1 phase motors |
| Pole |
3 Pole 3 NO |
| Coil |
230 VAC 50/60 Hz |
| Impedance |
2.5 mOhm at 50 Hz – Ith 25 A power circuit |
| Voltage limit |
0.3…0.6 Uc drop-out at 140 °F (60 °C), AC 50/60 Hz
0.8…1.1 Uc operational at 140 °F (60 °C), AC 50 Hz
0.85…1.1 Uc operational at 140 °F (60 °C), AC 60 Hz |
| Power |
70 VA at 68 °F (20 °C) (cos ϕ 0.75) 60 Hz
70 VA at 68 °F (20 °C) (cos ϕ 0.75) 50 Hz |
| mechanical |
| Protection |
Vibrations contactor open 2 Gn, 5…300 Hz
Vibrations contactor closed 4 Gn, 5…300 Hz
Shocks contactor open 10 Gn for 11 ms
Shocks contactor closed 15 Gn for 11 ms |
| Dimension |
H77 X W45 X D86 mm |
| Weight |
325 g |
| Safety |
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Wire stripping strength |
Control circuit: screw clamp terminals 2 cable(s) 0…0 in² (1…2.5 mm²) – cable stiffness: flexible – with cable end
Power circuit: screw clamp terminals 1 cable(s) 0…0.01 in² (1…4 mm²) – cable stiffness: flexible – with cable end
Control circuit: screw clamp terminals 1 cable(s) 0…0.01 in² (1…4 mm²) – cable stiffness: flexible – without cable end
Control circuit: screw clamp terminals 2 cable(s) 0…0.01 in² (1…4 mm²) – cable stiffness: flexible – without cable end
Control circuit: screw clamp terminals 1 cable(s) 0…0.01 in² (1…4 mm²) – cable stiffness: flexible – with cable end
Control circuit: screw clamp terminals 1 cable(s) 0…0.01 in² (1…4 mm²) – cable stiffness: solid – without cable end
Control circuit: screw clamp terminals 2 cable(s) 0…0.01 in² (1…4 mm²) – cable stiffness: solid – without cable end
Power circuit: screw clamp terminals 1 cable(s) 0…0.01 in² (1…4 mm²) – cable stiffness: flexible – without cable end
Power circuit: screw clamp terminals 2 cable(s) 0…0.01 in² (1…4 mm²) – cable stiffness: flexible – without cable end
Power circuit: screw clamp terminals 2 cable(s) 0…0 in² (1…2.5 mm²) – cable stiffness: flexible – with cable end
Power circuit: screw clamp terminals 1 cable(s) 0…0.01 in² (1…4 mm²) – cable stiffness: solid – without cable end
Power circuit: screw clamp terminals 2 cable(s) 0…0.01 in² (1…4 mm²) – cable stiffness: solid – without cable end |
| Tightening torque |
Power circuit: 15.04 lbf.in (1.7 N.m) – on screw clamp terminals – with screwdriver flat Ø 6 mm
Power circuit: 15.04 lbf.in (1.7 N.m) – on screw clamp terminals – with screwdriver Philips No 2
Control circuit: 15.04 lbf.in (1.7 N.m) – on screw clamp terminals – with screwdriver flat Ø 6 mm
Control circuit: 15.04 lbf.in (1.7 N.m) – on screw clamp terminals – with screwdriver Philips No 2 |
| Auxilary contact |
1 NO + 1 NC |
| material |
| Coil |
Without built-in suppressor module |
| Color |
Grey |
| Electrical durability |
2 Mcycles 12 A AC-3 at Ue <= 440 V
0.8 Mcycles 25 A AC-1 at Ue <= 440 V |
| Mounting support |
Rail
Plate |
| envorinmental |
| Protection |
TH conforming to IEC 60068-2-30 |
| Standard compliance |
EN/IEC 61008-1 |
| IP rotection |
IP20 front face conforming to IEC 60529 |
| Certification |
LROS (Lloyds register of shipping) RINA GOST BV CCC DNV GL |
| Temperature range |
-40 °C to +70 ° |
| Standard |
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508 |